Flex 12EX System Instruction Manual
December 2013
Page 34 of 48
RELAY FUNCTIONS
1 324 756 8
4.2.4 Dip-Switch Settings
4.2.4.1 Interlocked Functions
Interlocked means the two adjacent push buttons cannot be activated simultaneously as
they will cancel each other out. Interlocked settings are usually applied to a crane’s forward
and reverse motions. Each dip-switch on the decoder module corresponds to one (1)
motion or two (2) adjacent push buttons (refer to Fig. 14 & 15 below). Only the first seven
(7) dip-switch positions are used (counting from left to right). The 8
th
dip-switch position
(far right) is not used.
(Fig. 14) (Fig. 15)
Manufacture preset
Dip
Settings
Function Descriptions
# of Relays
Used
0000000 Normal (single speed only, F2 & R2 relays not used)
2
0000001
Closed/Closed Relay Action at 2
nd
Speed (separate 2
nd
speed
relay)
4
0000010
Closed/Closed Relay Action at 2
nd
Speed (shared 2
nd
speed
relay)
3
0000011
Opened/Closed Relay Action at 2
nd
Speed (separate 2
nd
speed
relay)
4
0000110 On (right button) & Off (left button)
2
0001000
On & Off affected by the e-stop command. When E-stop
command is initiated, the Off relay is activated.
2
0001001
On + Start / Off + Start -- Prior to pressing the button you must
first rotate and hold the power key switch at START position to
activate On or Off relays.
2
0001010 FWD/REV toggled (latched).
2
0001011
FWD/REV toggled (latched) and affected by the E-stop
command.
2
0000111 Safety Magnet On & Off
2
0100001 Closed/Closed + Brake
4
0100010 Closed/Closed Relay Action + Brake
3
0100011 Opened/Closed Relay Action + Brake
4